Skip to content

Commit ce752bb

Browse files
authored
Merge pull request #2113 from arduino/mcmchris/opta-analog-exp/datasheet-fix
Opta Analog Expansion Datasheet Minor Fix
2 parents 3b62950 + 662a8e8 commit ce752bb

File tree

1 file changed

+14
-20
lines changed
  • content/hardware/07.opta/opta-family/opta-analog-exp/datasheet

1 file changed

+14
-20
lines changed

content/hardware/07.opta/opta-family/opta-analog-exp/datasheet/datasheet.md

+14-20
Original file line numberDiff line numberDiff line change
@@ -27,16 +27,16 @@ The Arduino Opta® Analog Expansion is designed for industrial standard machiner
2727
## Features
2828
### General Specifications Overview
2929

30-
| Characteristics | Details |
31-
| --------------------------- | ---------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- |
32-
| Supply Voltage | 12...24 V |
33-
| Reverse polarity protection | Yes |
34-
| ESP protection | Yes |
35-
| Overvoltage protection | Yes (up to 40 V) |
36-
| Channels | 8x: I1, I2, I3, I4, O1, I5, I6, O2 |
37-
| Channels functionalities | I1 and I2: Programmable inputs (Voltage, Current, RTD2 wires, RTD3 wires), Programmable outputs (Voltage and current) - I3, I4, O1, I5, I6, O2: Programmable inputs (Voltage, Current, RTD2 wires), Programmable outputs (Voltage and current) |
38-
| Degree of Protection | IP20 |
39-
| Certifications | FCC, CE, UKCA, cULus, ENEC |
30+
| Characteristics | Details |
31+
| -------------------------------- | ---------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- |
32+
| Supply Voltage | 12...24 V |
33+
| Reverse polarity protection | Yes |
34+
| ESP protection | Yes |
35+
| Transient overvoltage protection | Yes (up to 40 V) |
36+
| Channels | 8x: I1, I2, I3, I4, O1, I5, I6, O2 |
37+
| Channels functionalities | I1 and I2: Programmable inputs (Voltage, Current, RTD2 wires, RTD3 wires), Programmable outputs (Voltage and current) - I3, I4, O1, I5, I6, O2: Programmable inputs (Voltage, Current, RTD2 wires), Programmable outputs (Voltage and current) |
38+
| Degree of Protection | IP20 |
39+
| Certifications | FCC, CE, UKCA, cULus, ENEC |
4040

4141
<div style="background-color: #FFFFE0; border-left: 6px solid #FFD700; margin: 20px 0; padding: 15px;">
4242
<strong>Note:</strong> Check the inputs and outputs detailed sections below for more information about the Analog Expansion channels use.
@@ -49,16 +49,10 @@ The Arduino Opta® Analog Expansion is designed for industrial standard machiner
4949
| Number of channels | 8x |
5050
| Channels programmable as inputs | I1, I2, I3, I4, O1, I5, I6, O2 |
5151
| Type of inputs accepted | Digital Voltage and Analog (Voltage, Current and RTD) |
52-
| Inputs overvoltage protection | Yes (Up to 40 V) |
52+
| Inputs overvoltage protection | Yes |
5353
| Antipolarity protection | No |
5454
| Analog Input resolution | 16 bits |
5555
| Noise Rejection | Optional noise rejection between 50 Hz and 60 Hz |
56-
| test | fjskfj |
57-
| | fjd |
58-
| | fjdklsfjd |
59-
| | fejdsklfakd |
60-
| | |
61-
6256

6357

6458
#### Voltage Input Mode
@@ -157,10 +151,10 @@ The Analog Expansion has four PWM output channels **(P1...P4)**. They are softwa
157151

158152
| V<sub>PWM</sub> Voltage | Details |
159153
| ------------------------ | --------------------- |
160-
| Source voltage supported | 8...40 VDC |
154+
| Source voltage supported | 8...24 VDC |
161155
| Period | Programmable |
162156
| Duty-cycle | Programmable (0-100%) |
163-
| | |
157+
164158

165159
#### Status LEDs
166160

@@ -228,7 +222,7 @@ We have tested setting all eight channels as outputs at 25 °C outputting more t
228222
<strong>Warning:</strong> In case the user needs a configuration with a deviation from the suggested one, will need to validate the system performance and stability before a deployment into a production environment.
229223
</div>
230224

231-
The PWM outputs are software configurable and for them to work you must provide the **V<sub>PWM</sub>** pin with the desired voltage between 8 and 40 VDC, you can set the period and duty-cycle by software.
225+
The PWM outputs are software configurable and for them to work you must provide the **V<sub>PWM</sub>** pin with the desired voltage between 8 and 24 VDC, you can set the period and duty-cycle by software.
232226

233227
### Expansion Port
234228
The expansion port can be used to daisy-chain several Opta® Expansions and additional modules. To be accessed needs to be freed up from its breakable plastic cover and the connection plug added between each device.

0 commit comments

Comments
 (0)