You signed in with another tab or window. Reload to refresh your session.You signed out in another tab or window. Reload to refresh your session.You switched accounts on another tab or window. Reload to refresh your session.Dismiss alert
Arduino Opta® Digital Expansions has eight *Normally Open* (NO) relays. For the **EMR** variant, eight powerful 6 A electromechanical relays capable of actuating on loads at a rated voltage of 250 VAC and up to a maximum switching voltage of 400 VAC, and for the **SSR** variant, eight fast 2 A solid state relays which are capable of actuating on DC loads at a rated voltage of 24 VDC.
164
+
Arduino Opta® Digital Expansions has eight *Normally Open* (NO) relays. For the **EMR** variant, eight powerful 6 A electromechanical relays capable of actuating on loads at a rated voltage of 250 VAC and up to a maximum switching voltage of 400 VAC, and for the **SSR** variant, eight fast 3 A solid state relays which are capable of actuating on DC loads at a rated voltage of 24 VDC.
165
165
166
166
The relay *Maximum Peak Current* is defined as the highest value of inrush current that the relay can endure without undergoing any permanent degradation of its characteristics due to the generated heat. The relay has to be able to hold up that maximum using a duty cycle of less or equal to 10% and for a time equal to or less than 0.5 s.
167
167
@@ -286,6 +286,7 @@ This device complies with part 15 of the FCC Rules. Operation is subject to the
Copy file name to clipboardExpand all lines: content/hardware/07.opta/opta-family/opta/tutorials/01.user-manual/content.md
+12-12
Original file line number
Diff line number
Diff line change
@@ -1835,7 +1835,7 @@ In the image below there is an example of the power wiring of the expansions:
1835
1835
1836
1836
#### Programmable Inputs
1837
1837
1838
-
The Opta™ Expansions have **16 analog/digital programmable inputs** accessible through terminals `I1` to `I16`.
1838
+
The Opta™ Expansions have **16x analog/digital programmable inputs** accessible through terminals `I1` to `I16`.
1839
1839
1840
1840
Both Ext D1608E and Ext D1608S variant inputs can be used as **digital** with a 0-24 VDC range or as **analog** inputs with a 0-24 VDC range. The inputs are capable of operating with 0-10V analog sensors as well as 0-24V sensors.
1841
1841
@@ -2195,7 +2195,7 @@ Expansion[0]: type DIGITAL [Mechanical], I2C address: 11
2195
2195
2196
2196
#### Outputs
2197
2197
2198
-
The Opta™ Expansions have **8 relay outputs** accessible through terminals pairs `1` to `8`.
2198
+
The Opta™ Expansions have **8x relay outputs** accessible through terminals pairs `1` to `8`.
2199
2199
2200
2200

2201
2201
@@ -2213,21 +2213,21 @@ Relay Output terminals are mapped as described in the following table:
2213
2213
| Relay 8 | 7 |
2214
2214
2215
2215
2216
-
The **Ext D1608E (EMR)** variant features 8 electromechanical relays with the following characteristics:
2216
+
The **Ext D1608E (EMR)** variant features 8x electromechanical relays with the following characteristics: