Modbus TCP with Portenta Machine Control & Opta™
intermediate
Learn to use Modbus TCP communication on a real industrial application using a Portenta Machine Control, Opta™, a temperature sensor, and the Arduino® PLC IDE.
Thermocouple
IEC-61131-3
PLC-IDE
Opta™
Christopher Mendez
hardware/05.pro-solutions/solutions-and-kits/portenta-machine-control
hardware/07.opta/opta-family/opta
plc-ide

Overview & Video Tutorial

In this tutorial, a Portenta Machine Control and an Opta™ micro PLC will be used as server and client respectively to share temperature information through Modbus TCP using the PLC IDE. The server will do the measurements using a type K thermocouple and the client will activate its relay outputs when a certain threshold is reached.

We have prepared a detailed guide in video format in case you are a visual learner.

<iframe width="100%" height="480" src="https://www.youtube.com/embed/mXZWJo_s6j8?si=Q2RJarWyFcRH5ude" title="YouTube video player" frameborder="0" allow="accelerometer; autoplay; clipboard-write; encrypted-media; gyroscope; picture-in-picture; web-share" allowfullscreen></iframe>

If you prefer to follow the tutorial in a written format, or need to review the steps and code done in the video tutorial, in the following sections you will find a step-by-step guide explaining how the temperature measurement and Modbus communication between both devices were done.

Goals

  • Learn how to measure temperature with the Portenta Machine Control using a thermocouple and the PLC IDE
  • Discover how to use the Modbus protocol over TCP/IP using the PLC IDE
  • Leverage Arduino Pro products for real industrial applications

Hardware and Software Requirements

Hardware

Software

Instructions

Solution Wiring

Real Application Wiring Setup

  • In the Portenta Machine Control: connect the thermocouple terminals to TP0 and TN0 respectively and the 24 VDC power supply to the 24-volt input and GND.

  • In the Opta™ micro PLC: connect the power supply to the respective inputs on the screw terminals.

  • Connect both the Portenta Machine Control and the Opta™ to your local network using ethernet cables.

Portenta Machine Control Setup

After downloading the PLC IDE, open it and create a new project for the Portenta Machine Control.

New project for the Portenta Machine Control

A license is needed for this product to be used with the PLC IDE, you can buy it directly from the Arduino store, and it will include the product key to activate the device.

Connect the Machine Control to the computer using a micro USB cable, the board needs to run a specific program (runtime) in order to interact with the PLC IDE. To flash it, select the device serial port and click on download.

Runtime program download

Once the runtime is flashed, navigate to On-line > Set up communication, open the Modbus properties and select the secondary serial port, then click "OK".

Modbus properties Modbus secondary serial port selection

Now, in the upper left corner, click on the Connect button and wait for the base program to be uploaded. A green Connected flag should appear in the lower right corner if everything goes well.

Connecting the board

The device will show its activation status, in this case, No License as it is the first time using it with the PLC IDE. To activate it, paste the product key you bought in the highlighted box and click on Activate.

Activation process

After the activation, the status should say OK. Now you are ready to start programming the Portenta Machine Control with the PLC IDE.

To learn more about the PLC IDE first setup, continue reading this detailed guide.

Modbus TCP - Server

For the Modbus TCP configuration, on the resources tab go to the Ethernet section. As noticed, the Modbus TCP Slave mode is always enabled, so you don't have to make any changes.

Modbus set to slave mode

Go to the sketch editor and uncomment the library and setup function code lines. As the IP, we must use the same as the Portenta Machine Control, as it is connected to your local network, you can find it on its configurations.

In this case, the following configurations are used:

// Enable usage of EtherClass, to set static IP address and other
#include <PortentaEthernet.h>
arduino::EthernetClass eth(&m_netInterface);

void setup()
{
	// Configure static IP address
	IPAddress ip(10, 0, 0, 157);    // Portenta Machine Control IP address
	IPAddress dns(10, 0, 0, 1);     // gateway IP address
	IPAddress gateway(10, 0, 0, 1); // gateway IP address
	IPAddress subnet(255, 255, 255, 0); 
	// If cable is not connected this will block the start of PLC with about 60s of timeout!
	eth.begin(ip, dns, gateway, subnet);

}

Network settings for Modbus TCP

Now create the variable that will be shared with the temperature sensor data in the network. Go to status variables and click on Add. Configure it as follows:

  • Name: temp_send
  • Address: 25000
  • PLC type: REAL

Temperature variable setup

Next go to Temperature probes and select the sensor type, for this tutorial, enable the thermocouple connected to the first channel by setting it to true.

Temperature probe configuration

Finally, go to the main program in project and match the temperature variable with the temperature sensor lectures as follows:

temp_send := sysTempProbes[0].temperature; 

Main program for the server

To check if everything is okay, click on compile, and if no error is shown, you can upload the code to your Portenta Machine Control.

Project compiled with no errors

Once uploaded, click on the Connect button again. Now you can monitor the temp_send variable in the Watch window dragging and dropping it from the Global shared variables in the project tab.

You should see the temperature value measured by the sensor inside the "Watch" window.

Live temperature measurement on the Machine Control

Opta™ Micro PLC Setup

Now the server is configured, create a new project, this time for the Opta™ micro PLC that will be the Client or Master.

New project for the Opta™

Upload the runtime for Opta™ by selecting its serial port and clicking on the Download button as before.

Uploading the runtime to the Opta™

Once the runtime is flashed, with your Opta™ connected to your router, search for its IP address on the router configurations.

On the PLC IDE, navigate to On-line > Set up communication, activate and then open the ModbusTCP properties. Add the Opta™ IP address, then click "OK".

Modbus TCP connection Modbus TCP IP setup

Now, in the upper left corner, click on the Connect button and wait for the base program to be uploaded. A green Connected flag should appear in the lower right corner if everything goes well.

Connecting the board

The Opta™ is Pre-Licensed so you don't have to buy any license to use it with the PLC IDE

If the Opta status says No License, click on the Activate PLC runtime button to activate it. Learn more about this case in this guide.

Modbus TCP - Client

With the Opta™ successfully connected to the PLC IDE, it is time to configure the Modbus TCP communication.

In the Ethernet tab, enable the Modbus TCP Master mode.

Modbus TCP Master mode enabled

Then right-click on the Ethernet tab, click on Add and select the Generic Modbus device.

Modbus Device Configuration - Step 1

On the Generic Modbus_1 device settings, enter the Server IP, the one from the Portenta Machine Control.

Modbus Device Configuration - Step 2

Right-click on the device and add the FC-04 Modbus function that will let us read the server input registers.

Modbus Device Configuration - Step 3

Now click on the function and in the general settings, enter the shared variable address that you defined earlier in the server, 25000 in this case.

Modbus Device Configuration - Step 4

In the Input Register tab, create a label for it, which could be temp_reg.

Label the register

Go to the sketch editor and uncomment the library and setup function code lines. As the IP, we must use the same as the Opta™.

In this case the following configurations are used:

void setup()
{
	// Configure static IP address
	IPAddress ip(10, 0, 0, 227);
	IPAddress dns(10, 0, 0, 1);
	IPAddress gateway(10, 0, 0, 1);
	IPAddress subnet(255, 255, 255, 0);
	// If cable is not connected this will block the start of PLC with about 60s of timeout!
	Ethernet.begin(ip, dns, gateway, subnet);
}

Network settings for Modbus TCP

Finally, define the Opta™ outputs behavior in function of the temperature read from the Portenta Machine Control. To do this, go to the resources tab > Relay Outputs and give a variable name to each relay, in this case, call them relay_1, relay_2, relay_3 and relay_4 respectively.

Outputs definitions

The same with the LED outputs, LED1, LED2, LED3 and LED4.

LEDs definitions

Now go to the main code in the Project tab. Create a variable by right-clicking on the local variables window and then insert, call it temp_local and integer as the type.

Create a local variable

In the code editor, match the local variable with the shared one sent by the Portenta Machine Control.

Once stored locally, design the logic to control the outputs as you want. In this case, four different temperature levels will be set to control each output with the temperature rise respectively. Copy and paste the following script into the main code section.

temp_local:= temp_reg;

IF temp_local >= 30 THEN
    relay_1 := TRUE;
    LED1 := TRUE;    
ELSE
    relay_1 := FALSE;
    LED1 := FALSE;
END_IF;

IF temp_local >= 50 THEN 
    relay_2 := TRUE;
    LED2 := TRUE;
ELSE
    relay_2 := FALSE;
    LED2 := FALSE;
END_IF;

IF temp_local >= 70 THEN 
    relay_3 := TRUE;
    LED3 := TRUE;
ELSE
    relay_3 := FALSE;
    LED3 := FALSE;    
END_IF;

IF temp_local >= 100 THEN 
    relay_4 := TRUE;
    LED4 := TRUE;
ELSE
    relay_4 := FALSE;
    LED4 := FALSE;    
END_IF;

Final code to control the outputs

With the final code written, compile the project and upload it the the Opta™ micro PLC.

Final Test

You can leave each device connected separately to the internet router or connect them together directly with one ethernet cable. The first option will let you update the preferred device remotely as you can access it through the local network.

Now you can expose the temperature sensor to some heat and monitor it from the PLC IDE. The Opta™ relay outputs and LEDs will close and turn on when the temperature surpasses the programmed thresholds respectively.

Testing the project

Conclusion

In this tutorial you learned how to communicate two Arduino PRO products using the Modbus TCP protocol, demonstrating a simple application of sharing temperature data to control the outputs of the devices.

As you can notice, the configuration process is very straightforward and the results were as expected, being a good starting point to adapt the work done here to create your own professional solution.

Next Steps

Extend your knowledge about the Portenta Machine Control, PLC IDE and the variety of industrial protocols it supports by following these tutorials: